Page 125: Figure 85 correct orientation of float switch, Humidifier, Correct orientation of float switch
3 humidifier, 1 infrared humidifier, 2 cleaning humidifier pan and float switch – Liebert Precision Cooling System DS User Manual Page 125: Figure 85 correct orientation of float switch, Humidifier, Correct orientation of float switch. Liebert HCR-PD- 273534 - 1 - 1 Features and Benefits The Liebert HCR heat exchangers are our new range of remote air-cooled condensers especially designed to be coupled with the Liebert CRV (A type) air conditioning units power supplied at 50Hz (CE market), within a standard range of external air temperature from-20°C to + 46°C.
Liebert HPM - PD - 273153 - Liebert HPM 6-205 kW Indoor Room Cooling Units C Version (single chilled water circuit) R Version (redundant - double chilled water circuit) Precision Cooling for Business-Critical Continuity PRODUCT DOCUMENTATION.
Maintenance
115
12.3 Humidifier
12.3.1 Infrared Humidifier
During normal humidifier operation, deposits of mineral solids will collect in humidifier pan and on
the float switch. These must be cleaned periodically to ensure proper operation. Frequency of cleaning
must be locally established since it is dependant on humidifier usage and local water quality. A spare
pan is recommended to reduce maintenance time at unit. The Liebert autoflush system can greatly
increase the time between cleanings, but does not eliminate the need for periodic checks and mainte-
nance (see iCOM user manual SL-18835 for autoflush setup). To help reduce excessive scaling in loca-
tions with difficult water quality, the use of Vapure is recommended (contact your local Emerson
representative).
12.3.2 Cleaning Humidifier Pan and Float Switch
Before turning off unit:
1. With unit operating, remove call for humidification at iCOM control.
2. Let blower operate 5 minutes to allow humidifier and water to cool.
3. If unit has a condensate pump, turn unit OFF at iCOM control.
4. Pull out humidifier standpipe in pan.
5. Inspect O-ring (replace if necessary).
6. Let pan drain and condensate pump operate (if applicable).
7. Disconnect power from unit.
8. Disconnect drain coupling from bottom of pan.
9. Remove thermostat from bottom of pan and retaining screws from sides of pan.
10. Slide pan out.
11. Loosen scale on side and bottom of pan with a stiff nylon brush or plastic scraper.
12. Flush with water
13. Carefully clean scale on float switch (make sure to reinstall correctly (seeFigure 85).
14. Reinstall pan, thermostat, standpipe, drain coupling and screws into humidifier.
15. Operate humidifier and check for leaks.
Figure 85 Correct orientation of float switch
Correct Switch Orientation
Incorrect Switch Orientation
DPN000996
Rev. 0
Precision Cooling
For Business-Critical Continuity™
Liebert®Variable Speed Upgrade Kits
Save Money Through Energy Efficient Operation
Get more efficient operation from your existing Chilled Water CRAC systems and quick payback through lower electricity costs and utility rebates.
The Variable Speed Drive (VSD/VFD) Upgrade is easily installed on your Liebert Deluxe System/3 Chilled Water systems, providing immediate results with lower electrical bills.
Typically, CRAC fans run at a constant speed and deliver a constant volume of air flow. Adding a Variable Speed Drive to the fan motor allows fan speed and power draw to be reduced as load decreases. A 20 percent reduction in fan speed provides almost 50 percent savings in fan power consumption.
VSD Features
Lowest Total Cost of
Ownership
Average payback on electricity costs is less than two years
Utility rebates available in some regions, providing even faster payback
Flexibility
Easy field installation by a factory trained technician
Higher Availability
Variable fan speed increases the life of the fan and motor
The VSD/VFD Motor | |
Upgrade Kit is Ideally Suited | |
For Chilled Water Models of | |
Liebert Deluxe System/3: | |
In IT operations looking for | |
fast, easy methods of cutting | |
costs long term | |
In IT operations looking for fast | |
ROI on cost saving initiatives | |
…a 20% reduction | |
in fan speed | |
provides almost | |
Liebert Deluxe System/3 Chilled | 50% savings in |
Water systems are easily field | power |
retrofitted with the VSD/VFD | |
motor kit to maximize energy | consumption |
efficiency |
Estimate your savings
The example below shows the cost to operate a floormount chilled water cooling unit at $0.10/kWh. Average energy savings offer full payback on VSD/VFD upgrades in two years or less.
$5,100/Year Savings
$3,400/Year $2,500/Year Savings
Savings
$1,700/Year Savings
Your Emerson Network Power/Liebert representative or local electric company can give you information about utility rebates for deploying energy efficiency initiatives. Rebates can lower the payback period to less than a year in many applications.
Real world payback
A customer in Texas
has completed a VSD/VFD upgrade, and utility savings based on site kW measurement readings are:
$3,400 energy cost savings per unit per year (34,427 kWh/unit/year)
$1,100 first year utility incentive per unit
$3,400 + $1,100 = $4,500 first year savings per unit.
A factory-trained service professional will assess your existing Liebert Deluxe
System/3 for VSD/VFD
compatibility.
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
Precision Cooling System
614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy
and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for
damages resulting from use of this information or for any errors or omissions.
© 2009 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.
® Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
Axle Assembly Components. Download buku pdf. Automatic Transmission. Hybrid Components. Toyota Owner manuals and warranty information are the keys toquality maintenance for your vehicle.
AP-20020 (01/09)
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Hpms User Guide
Precision Cooling
Liebert Ds Precision Cooling System
Racks & Integrated Cabinets
Liebert Hpm Precision Cooling User Manual Software
Services
Surge Protection
EmersonNetworkPower.com
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2009 Emerson Electric Co.